HPMOM5
6 Fused Output Distribution with Fire Panel Interface
This multi-output power distribution module converts one non-power limited 12 VDC or 24 VDC voltage input to 6 power limited outputs. Each output can be used to power magnetic locks, electric strikes, magnetic door holders, etc. Outputs switch together and operate both fail-safe and
fail-secure. Activation is through normally open or normally closed supervised input or the polarity reversal from a fire alarm control panel.
A Form C dry output relay will enable HVAC shutdown, elevator recall or trigger auxiliary devices. Class 2 current rated at 2.5 A per output.
Diagnostic LEDs per circuit. Power and input trigger LEDs. Power fail supervision relay is Form C rated 1 A @ 28 VDC/115 VAC.
Dimensions: 5.3" H x 3.5" W x 1" D (13.5 cm H x 8.9 cm W x 2.5 cm D).