Room Temperature Sensors
The STR150 is equipped with an LCD that displays the different functions of the module.
The STR150 is designed to be used together with:
• TAC Xenta 101-VF SW-version 1.2 or later
• TAC Xenta 102-ES SW-version 1.2 or later
• TAC Xenta 103-A SW-version 1.2 or later
• TAC Xenta 104-A SW-version 1.2 or later
TECHNICAL DATA Ambient conditions: Storage -20 to +80 ºC (-4 to 176 ºF) max 90% RH Operation 0 to +50 ºC (32 to 122 ºF) max 90% RH Mechanical Enclosure rating IP20 / NEMA1 Enclosure material PC/ABS plastic Weight 85 g (0.19 lb) Dimensions:(mm) 116X84X24 Standards: EMC EN 50081-1, EN 50082-1 FCC part 15 class B Safety Standard UL 916 (pending) Flammability rating UL 94V-0 Wiring Cable type Twisted pair, unshielded Cable size Min 0.7 mm2 (19 AWG) Distance Max 30 m (100 ft) Temperature range Detection and display 5 - 45 °C (41 - 113 °F) Transferred to X100 8 - 33.4 °C (46.4 – 92.1 °F) Accuracy at 15-30 °C (60-85 °F), +/- 0.5 °C (0.9 °F) Sensor Time Constant 9 min. Temperature resolution, room and setpoint Display 0.1 or 0.5 °C (0.2 or 1 °F) Temperature updates Display 10 sec. Transferred to X100 10 sec. Setpoint Value Range 15-30 °C (59 – 86 °F) Span +/- 0 to +/- 5°C (+/- 0 to +/- 10°F)